This article continues with Chapter 6, Swinging Doors with Builders
Hardware found in the NFPA 80 Standard for Fire Doors and Other Opening
Protectives 2007 edition. This information is in Chapter 2 of the 1999
edition. We will cover some of the highlights of hinges.
Requirements for hinge thickness and sizes are found in Table
6.4.3.1. Included in the table is the minimum hinge sizes and thickness
for doors 1 3/4 inches thick and 1 3/8 inch thick with hourly ratings.
The information in the table is the same as presented in the 1999
edition. The 1999 edition listed some additional notes below the table
and the 2007 edition incorporates those same notes into the body of the
standard. The information is the same.
This standard is where we get the number of hinges required for a
rated door. 6.4.3.1.1 Indicates doors up to 60 inches in height shall be
provided with two hinges and an additional hinge for each additional 30
inches of door height or fraction thereof. 6.4.3.1.1.2 tells us where
spring hinges are used, at least two shall be provided. Spring hinges
shall be labeled and meet the requirements of the American National
Standards Institute/Builders Hardware Manufacturers Association
ANSI/BHMA A156.17, Standard for Self Closing Hinges and Pivots. BHMA
standards are available from BHMA or the Door and Hardware Institute.
Except for spring hinges, all hinges or pivots shall be of the ball
bearing type. Other antifriction bearing surfaces shall be permitted if
they meet the requirements of ANSI/BHMA A156.1, Standard for Butts and
Hinges.
Hinges 4 1/2 inches high and 0.180 inches thick are permitted for
use on wide and heavy doors or doors that are subjected to heavy use or
unusual stress.
Looking at attaching hinges to doors, it begins with a statement
that hinges are to be secured in accordance with the manufacturer's
installation instructions. In addition to that general statement, it
goes into further detail. Mortise hinges shall be secured to
reinforcements in the doors with steel machine screws. Hinges must also
be secured to the frame with steel screws. The screws for frames can
vary depending on the material used for the manufacture of the labeled
door frames. The manufacturer's instructions and published listings
for labeled door frames shall be referenced for specific screw
requirements.
Attaching mortise hinges to wood and plastic covered composite
doors or wood core doors requires pilot holes of 5/32 inches diameter to
be drilled prior to screw installation and the use of No. 12 x 1 1/4
inch flat, threaded-to-the-head steel wood screws.
6.4.3.4 permits shimming of hinges to meet required clearances with
steel shims.
Locks or latches is the next subject covered in this chapter. It
begins with two important requirements:
6.4.4.1 The first states, Only labeled locks and latches or labeled
fire exit hardware (panic devices) meeting both life safety requirements
and fire protection requirements shall be used.
6.4.4.2 The second, Fire exit hardware shall be installed only on
fire doors bearing the mark "Fire Door to be equipped with Fire
Exit Hardware."
Further reading reveals additional requirements for exit devices.
Fire exit hardware shall be labeled for both fire and panic.
Fire exit hardware shall have a permanently attached label that
bears the serial number and shows the manufacturer's name and type
of approval.
The label shall differentiate between panic hardware, which is not
acceptable for use on fire doors, and fire exit hardware.
All single doors and active leaves of pairs of doors shall be
provided with an active latch bolt that cannot be held in a retracted
position as specified in the individual manufacturer's published
listings.
Latching arrangements that do not provide positive latching in the
normal mode shall be permitted to be used provided that, in afire
emergency, the door becomes positively latched by means of an automatic
fail-safe device that is activated by an automatic fire detector.
Where both leaves are required for exit purposes, they shall be
provided with labeled fire exit hardware.
Where permitted by the Authority Having Jurisdiction, AHJ, pairs of
doors not provided with an astragal shall be permitted to have labeled
fire exit hardware and an open back strike installed on the inactive
leaf, and either labeled fire exit hardware or any labeled latch capable
of being opened by one obvious operation from the egress side installed
on the active leaf.
The information presented in this article is highlights from the
standard. You must consult the standard for further information that may
not be included but may be relevant to your project.
[GRAPHIC OMITTED]
COPYRIGHT 2007 Door and Hardware
Institute Reproduced with permission of the copyright holder. Further reproduction or distribution is prohibited without permission.
Copyright 2007, Gale Group. All rights
reserved. Gale Group is a Thomson Corporation Company.
NOTE: All illustrations and photos have been removed from this article.